Troubleshooting by Indication on the Remote Controller
SiUS28-902_a
93
Troubleshooting
∗
1: Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the P.C.B. and check the continuity between the
connector pins.
(Normal)
: Continuity
×: No continuity
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
Approx.
300
Ω
×
Approx.
150
Ω
×
2. Yellow
×
Approx.
300
Ω
×
Approx.
150
Ω
3. Orange
×
Approx.
150
Ω
×
4. Blue
×
Approx.
150
Ω
5. Red
×
6. Brown