Troubleshooting by Indication on the Remote Controller
SiUS28-902_a
133
Troubleshooting
3.37 “
U3
” Check Operation not Executed
Remote
Controller
Display
U3
Applicable
Models
RZQ18~30PVJU
Method of
Malfunction
Detection
Check operation is executed or not
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
Has the
check operation
performed on O
u
tdoor
u
nit P.C.B.?
P
u
sh the BS4 on P.C.B. on the
master o
u
tdoor
u
nit for 5 seconds
or more to exec
u
te check
operation.
Replace the main P.C.B. on the
o
u
tdoor
u
nit.
N
O
YES
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
the connector, or parts co
u
ld
b
e damaged.