Troubleshooting by Indication on the Centralized Remote Controller
SiUS28-902_a
149
Troubleshooting
4.5
“
MC
” Address Duplication, Improper Setting
Remote
Controller
Display
MC
Applicable
Models
Centralized remote controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Address duplication of centralized remote controller
Troubleshooting
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
the connector, or parts co
u
ld
b
e damaged.
Are t
w
o
or more centralized
remote controllers
connected?
Disconnect all centralized
remote controllers except one,
and reset the po
w
er s
u
pply of
the centralized remote
controller.
Reset po
w
er s
u
pply of the
centralized remote controller.
N
O
YES