Troubleshooting by Indication on the Remote Controller
Troubleshooting
92
3.6
“
A9
” Indoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E)
Remote
Controller
Display
A9
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Malfunction of moving part of electronic expansion valve
Defect of indoor unit P.C.B.
Defect of connecting cable
Troubleshooting
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
the connector, or parts co
u
ld
b
e damaged.
After connecting, t
u
rn the po
w
er
s
u
pply off and then
b
ack on.
Replace the mo
v
ing part of the
electronic expansion
v
al
v
e.
YES
YES
N
O
N
O
Replace the connecting ca
b
le.
If yo
u
t
u
rn the po
w
er s
u
pply off
and t
u
rn on again, and it still does
not help, replace the indoor
u
nit
P.C.B.
N
O
YES
The
electronic
expansion
v
al
v
e is
connected to X7A of the
indoor
u
nit
P.C.B.
N
ormal
w
hen coil check
(
*
1) of the mo
v
ing part of
the electronic expansion
v
al
v
e is
checked.
The connecting
ca
b
le is short-circ
u
ited or
disconnected.
Summary of Contents for SkyAir FCQ18PVJU
Page 1: ...Split System Air Conditioners SkyAir Inverter R 410A Heat Pump 60Hz P Series SiUS28 902_a...
Page 44: ...Other Control SiUS28 902_a 37 Function...
Page 81: ...SiUS28 902_a Troubleshooting by Remote Controller Troubleshooting 74...
Page 185: ...SiUS28 902 Precautions for New Refrigerant R 410A Precautions for New Refrigerant R 410A 178...