Special Control
SiUS28-902_a
27
Function
3.6
Stopping Operation
When the system is down the actuator stops/clears all operations.
3.6.1 When System is in Stop Mode
Actuator
Operation
Compressor
OFF
Outdoor unit fan
OFF
Four-way valve
Keep former condition.
Main electronic expansion valve (EV1)
0 pls
Subcooling electronic expansion valve (EV2)
0 pls
Hot gas bypass valve (SVP)
OFF
Receiver gas discharging valve (SVG)
OFF
Ending conditions
Indoor unit thermostat is turned ON.