5.6
View of Operations of Swing Flaps
Swing flaps work as following.
Fan
Flap control
FCQ
FHQ
FAQ
He
a
ti
n
g
Hot-start from
defrosting
Swinging
OFF
Level
Level
Level
Setting the wind direction
OFF
Level
Level
Level
Defrosting
Swinging
OFF
Level
Level
Level
Setting the wind direction
OFF
Level
Level
Level
Thermostat is off
Swinging
LL
Level
Level
Level
Setting the wind direction
LL
Level
Level
Level
Hot-start from the
state that the
thermostat is off
Swinging
LL
Level
Level
Level
Setting the wind direction
LL
Level
Level
Level
Halt
Swinging
OFF
Level
Level
Level
Setting the wind direction
OFF
Level
Level
Level
Co
o
lin
g
Thermostat of
microcomputer-dry
is on
Swinging
L
*1
Swinging
Swinging
Swinging
Setting the wind direction
L
*1
Set up
Set up
Set up
Thermostat of
microcomputer-dry
is off
Swinging
OFF
or
L
Swinging
Swinging
Swinging
Setting the wind direction
Set up
Set up
Set up
Cooling thermostat
is off
Swinging
Set up
Swinging
Swinging
Swinging
Setting the wind direction
Set up
Set up
Set up
Set up
Halt
Swinging
OFF
Level
Level
Level
Setting the wind direction
OFF
Set up
Level
Level
Microcomputer is
controlled (including
the cooling state)
Swinging
L
Swinging
Swinging
Swinging
Setting the wind direction
L
Set up
Set up
Set up
* 1. Only in FCQ case, L or LL.
Summary of Contents for SkyAir FCQ18PVJU
Page 1: ...Split System Air Conditioners SkyAir Inverter R 410A Heat Pump 60Hz P Series SiUS28 902_a...
Page 44: ...Other Control SiUS28 902_a 37 Function...
Page 81: ...SiUS28 902_a Troubleshooting by Remote Controller Troubleshooting 74...
Page 185: ...SiUS28 902 Precautions for New Refrigerant R 410A Precautions for New Refrigerant R 410A 178...