![background image](http://html2.mh-extra.com/html/daikin/skyair-fcq18pvju/skyair-fcq18pvju_service-manual_4705640054.webp)
Field Setting
SiUS28-902_a
47
Test Operation
3. Field Setting
3.1
Field Setting from Remote Controller
Individual functions of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
An incorrect setting may cause malfunction.
3.1.1 Wired Remote Controller <BRC1D71>
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
1. When in the normal mode, push the “
” button (
N
) for 4 seconds or more, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “
” button (
O
).
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), push the “
” button (
P
) and select the INDOOR UNIT NO. to be set. (This
operation is unnecessary when setting by group.)
4. Push the “
” upper button (
Q
) and select FIRST CODE NO.
5. Push the “
” lower button (
R
) and select the SECOND CODE NO.
6. Push the “
” button (
S
) once and the present settings are SET.
7. Push the “
” button (
T
) to return to the NORMAL MODE.
Example
When setting the filter sign time to “Filter Contamination Heavy” in all group unit setting, set the
Mode No. to “10”, first code No. to “0” and second code No. to “02”.
TEST
SETTIING
Unit NO.
UNIT NO.
SECOND
CODE NO.
MODE NO.
FIELD
SET
MODE
FIRST
CODE NO.
2P068938
1 7
6
3
4
5
2
TEST
TEST
Summary of Contents for SkyAir FCQ18PVJU
Page 1: ...Split System Air Conditioners SkyAir Inverter R 410A Heat Pump 60Hz P Series SiUS28 902_a...
Page 44: ...Other Control SiUS28 902_a 37 Function...
Page 81: ...SiUS28 902_a Troubleshooting by Remote Controller Troubleshooting 74...
Page 185: ...SiUS28 902 Precautions for New Refrigerant R 410A Precautions for New Refrigerant R 410A 178...