Troubleshooting by Indication on the Remote Controller
Troubleshooting
102
3.15 “
E3
” Outdoor Unit: Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RZQ18~30PVJU
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 580 psi
Reset pressure:
435 psi
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit P.C.B.
Instantaneous power failure
Faulty high pressure sensor