Field Setting
SiUS28-902_a
55
Test Operation
3.2
Field Setting from Outdoor Unit
3.2.1 Setting by push-button switches
The following settings are made by pushbutton switches on P.C.B.
(Factory setting)
There are the following three setting modes.
Setting mode 1 (H1P off)
Initial status (when normal) : Also indicates during “abnormal”.
Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Mode changing procedure
Mode changing procedure
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED display
h
h
k
h
h
h
h
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
Setting mode 1
Monitor mode
H1P
Push the BS1(MODE button)
one time.
Blinking
MODE
MODE
Off
H1P
Setting mode 2
MODE
On
H1P
Push and hold the BS1
(MODE button) for 5 seconds.
Push the BS1(MODE button) one time.
(Normal)
Using the MODE button, the modes can be changed as follows.
Check item selection (Set)
Contents display
Monitor mode
Setting mode 1
(Initial condition)
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Setting item selection (Set)
Setting mode 2
(Set): Select mode with BS2 (SET button) in each selection step.
Setting condition
selection (Set)
Setting condition
(Contents) display
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Press BS1 (MODE button) one time.
Press BS1 (MODE button) one time.
Press BS1(MODE button) one time.
Press BS1 (MODE button) for more than 5 sec.
Summary of Contents for SkyAir FCQ18PVJU
Page 1: ...Split System Air Conditioners SkyAir Inverter R 410A Heat Pump 60Hz P Series SiUS28 902_a...
Page 44: ...Other Control SiUS28 902_a 37 Function...
Page 81: ...SiUS28 902_a Troubleshooting by Remote Controller Troubleshooting 74...
Page 185: ...SiUS28 902 Precautions for New Refrigerant R 410A Precautions for New Refrigerant R 410A 178...