Components
Service manual
114
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
a
A
A
Wall mounted indoor unit
a
Connector S102
a
A
A
Floor standing indoor unit
a
Connector S102
Is the measured voltage on the indoor
unit power PCB correct?
Action
Yes
power PCB and continue with the next
procedure.
No
Replace the indoor unit power PCB, see
To check if the correct spare part is installed
Prerequisite:
First perform all earlier checks of the indoor unit main PCB, see
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.