Components
Service manual
58
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
A mechanical lock is present on the
compressor?
Action
No
Perform an mechanical check of the
compressor, see
57].
To perform a mechanical check of the compressor
Prerequisite:
First perform an auditive check of the compressor, see
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Wait until the rectifier voltage is below 10 V DC.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Visually check:
▪
For oil drops around the compressor. Locate and fix as needed.
▪
Pipes for signs of damage. Replace pipes as needed.
3
Check that the compressor bolts are correctly fixed. Fix as needed.
4
Check that the compressor wire terminals cover is correctly installed and
fixed. Correct as needed.
5
Check the compressor dampers for any damage.
a
a
a
Damper
INFORMATION
The compressor dampers may look different.