Components
Service manual
70
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
a
a
A
A
Class 20~35 unit
a
Compressor pipe
a
a
A
A
Class 42~71 unit
a
Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
9
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
10
Install the putty on the compressor accumulator.
11
Install the compressor thermal protector, see
12
Connect the Faston connectors to the compressor wire terminals U, V and W