![Daikin Perfera RXM20R Service Manual Download Page 27](http://html1.mh-extra.com/html/daikin/perfera-rxm20r/perfera-rxm20r_service-manual_4700072027.webp)
3
|
Troubleshooting
Service manual
27
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
8
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
207].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.15 F3-00 – Outdoor unit: Malfunction of discharge pipe temperature
Trigger
Effect
Reset
Discharge pipe thermistor
detects a too high
temperature.
Unit will NOT stop
operating.
Automatic reset when
temperature drops
normal level.
If the error re-occurs too
soon: unit will stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge or shortage.
3
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
207].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
4
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
5
Perform a check of the 4‑way valve. See
Possible cause:
Faulty 4‑way valve.
6
Perform a check of the expansion valve. See
Possible cause:
Faulty expansion valve.
7
Perform a check of the main PCB. See
125].
Possible cause:
Faulty main PCB.
8
Perform
a
check
of
all
refrigerant
side
thermistors.
See
192].
Possible cause:
Faulty refrigerant side thermistor(s).