![Daikin Perfera RXM20R Service Manual Download Page 53](http://html1.mh-extra.com/html/daikin/perfera-rxm20r/perfera-rxm20r_service-manual_4700072053.webp)
4
|
Components
Service manual
53
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
4.1.2 Repair procedures
To remove the 4-way valve coil
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
Prerequisite:
If needed, remove any parts to create more space for the removal of
the 4‑way valve coil.
1
Remove the screw and remove the 4‑way valve coil from the 4‑way valve
body.
a
b
c
A
A
Class 20~35 unit
a
Screw
b
4‑way valve coil
c
4‑way valve body
A
c
a
b
A
Class 42~71 unit
a
Screw
b
4‑way valve coil
c
4‑way valve body
2
Cut all tie straps that fix the 4‑way valve coil harness.
3
Unplug the 4-way valve connector from the appropriate PCB.
4
To install the 4‑way valve coil, see
To remove the 4-way valve body
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see