Components
Service manual
101
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
2
153].
3
Remove the 2 screws and remove the upper air outlet assembly.
a
a
b
c
f
f
g
d
e
a
Screw (upper air outlet assy)
b
Upper air outlet assy
c
Drain hose
d
Damper motor wiring harness
e
Screw (tie strap)
f
Screw (lower air outlet assy)
g
Lower air outlet assy
4
Put a small drain pan (or container) under the drain hose.
5
Remove the screw from the fixation bracket and pull the drain hose
downwards to remove it from the indoor unit.
6
Route the damper motor wiring harness out of the harness retainers and
remove the screw to disconnect the tie strap from the unit.
7
Remove the 2 screws and remove the lower air outlet assembly.
8
Remove the screw and remove the plate from the indoor unit heat exchanger.
a
f
d
e
b
c
e
a
Screw (plate)
b
Plate
c
Indoor unit heat exchanger
d
Piping fixture
e
Flared joint
f
Screw (ground wire)