SiBE04-302
Control Specification
Function and Control
57
3.13 Malfunctions
3.13.1
Sensor Malfunction Detection
Sensor malfunction may occur either in the thermistor or current transformer (CT) system.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Fin thermistor
4. Outdoor air thermistor
Relating to CT Malfunction
When the output frequency is more than 62 Hz and the input current is less than 0.5A, carry out
abnormal adjustment.
3.13.2 Detection of
Over Load
and
Over Current
Outline
In order to protect the inverter, detect an excessive output current, and for protecting
compressor, monitor the OL operation.
Detail
If the OL (compressor head) temperature exceeds 120~130°C (depending on the
model), the compressor gets interrupted.
If the inverter current exceeds 22 A, the compressor gets interrupted too.
3.13.3
Insufficient Gas Control
Outline
If a power consumption is below the specified value in which the frequency is higher than the
specified frequency, it must be regarded as gas insufficient.
In addition to such conventional function, if the discharge temperature is higher than the target
discharge pipe temperature, and the electronic expansion valve is fully open (55 pulses) more
than the specified time, it is considered as an insufficient gas.
With the conventional function, a power consumption is weak comparing with that in the normal
operation when gas is insufficient, and gas insufficiency is detected by checking a power
consumption.
When operating with insufficient gas, although the rise of discharge pipe temperature is great
and the electronic expansion valve is open, it is presumed as an insufficient gas if the discharge
pipe temperature is higher than the target discharge pipe temperature.
Detail
Judgment by Input Current
When an output frequency is exceeds 55 Hz (FTK(X)S, ATK(X)S series: 65Hz) and the input
current is less than specified value, the adjustment is made for insufficient gas.
Judgment by Discharge Pipe Temperature
When discharge pipe temperature is 30°C higher than target value and the electronic expansion
value opening is 55 plus (max.), the adjustment is made for insufficient gas.
Frequency
Power consumption
Insufficient gas zone
55 Hz
(R2834)
Gas insufficient
zone
(R1391)
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...