SiBE04-302
Others
Others
177
1.2
Jumper Settings
1.2.1 When Two Units are Installed in One Room
How to set the different addresses
When two indoor units are installed in one room, the two wireless remote controllers can be
set for different addresses.
PCB in the indoor unit
Remove the front panel.
Remove the sensor parts cover (2-screws), then remove the electric parts box (1-screw).
Slide the metallic cover to remove it. (4-claws on the electric parts box.)
Cut the jumper
JA
on PCB.
Wireless remote controller
Cut the jumper
J4
.
1.2.2 Jumper Setting
Wireless
remote
controller
Address
J4
CUT
EXIST
1
2
JA
ADDRESS
J4
ADDRESS:
CUT
EXIST
1
2
JA
JB
JC
Metallic cover
Sensor
parts cover
PCB
Electric
parts box
Claws (4 points)
(R2587)
Jumper
(On indoor PC
Board)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto start
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings are
cleared.
JB
Fan speed setting
when compressor is
OFF on thermostat.
Fan speed setting ;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...