SiBE04-302
Main Functions
Function and Control
41
1.10 Other Functions
1.10.1
Hot Start Function
Heat Pump Only
In order to prevent the cold air blast that normally comes when heating is started, the
temperature of the heat exchanger of the indoor unit is detected, and either the air flow is
stopped or is made very weak thereby carrying out comfortable heating of the room.
*The cold air blast is also prevented using a similar control when the defrosting operation is
started or when the thermostat gets turned ON.
1.10.2
Signal Receiving Sign
When the indoor unit receives a signal from the remote controller, the unit emits a signal
receiving sound.
1.10.3
ON/OFF Button on Indoor Unit
An ON/OFF switch is provided on the front panel of the unit. Use this switch when the remote
controller is missing or if its battery has run out.
Every press of the switch changes from Operation to Stop or from Stop to Operation
Push this button once to start operation. Push once again to stop it.
This button is useful when the remote controller is missing.
The operation mode refers to the following table.
In the case of multi system operation, there are times when the unit does not activate with
this button.
1.10.4
Photocatalytic Deodorizing Filter
Photocatalytic Deodorizing Filter demonstrates powerful oxidation characteristics when
subjected to harmless ultraviolet light. Photocatalytic deodorizing power is recovered simply by
exposing the filter to the sun for 6 hours once every 6 months.
1.10.5
Air-Purifying Filter
A double structure made up of a bacteriostatic filter and an Air-Purifying Filter traps dust,
mildew, mites, tobacco smoke, and allergy-causing pollen. Replace the Air-Purifying Filter once
every 3 months.
1.10.6
Mold Proof Air Filter
The filter net is treated with mold resisting agent TBZ (harmless, colorless, and odorless). Due
to this treatment, the amount of mold growth is much smaller than that of normal filters.
1.10.7
Self-Diagnosis Digital Display
The microcomputer continuously monitors main operating conditions of the indoor unit, outdoor
unit and the entire system. When an abnormality occur, the LCD remote controller displays error
code. These indications allow prompt maintenance operations.
1.10.8
Auto-restart Function
Even if a power failure (including one for just a moment) occurs during the operation, the
operation restarts in the condition before power failure automatically when power is restored.
(Note) It takes 3 minutes to restart the operation because the 3-minute standby function is
activated.
Mode
Temperature setting
Air flow rate
Cooling Only
COOL
22ºC
AUTO
Heat Pump
AUTO
25ºC
AUTO
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...