![Daikin ARK25BVMB Service Manual Download Page 104](http://html.mh-extra.com/html/daikin/ark25bvmb/ark25bvmb_service-manual_501295104.webp)
SiBE04-302
Troubleshooting
Service Diagnosis
95
4.4
Fan Motor (AC Motor) or Related Abnormality
Remote
Controller
Display
A6
Method of
Malfunction
Detection
The rotation speed detected by the hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Malfunction
Decision
Conditions
When the detected rotation speed is less than 50% of the HH tap under maximum fan motor
rotation demand.
Supposed
Causes
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Operation halt due to faulty capacitor of the fan motor.
Detection error due to faulty indoor unit PCB.
Troubleshooting
Check No.16
Refer to P.127
Rotate the fan by hand.
Check No. 16
Check hall IC
Operate the fan.
Does it rotate?
NO
Does it rotate smoothly?
Is there an output?
Is it at the rated voltage?
Is there conductivity?
NO
Check the capacitor's conductivity
Check the fan motor voltage.
(immediately after re-start)
Is it at the rated voltage?
Check the fan motor voltage.
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
Replace the fan motor or indoor unit
PCB.
Replace the fan motor
∗
2 Measure the voltage between the
red and black lead wires of the fan
motor, and check if the maximum
voltage reaches the rated voltage.
Replace indoor unit PCB (1).
Replace the fan motor.
Replace the indoor unit PCB (1)
Replace the capacitor.
(Replace PCB (1).)
Replace the fan motor.
(R1946)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...