![Daikin ARK25BVMB Service Manual Download Page 60](http://html.mh-extra.com/html/daikin/ark25bvmb/ark25bvmb_service-manual_501295060.webp)
SiBE04-302
Control Specification
Function and Control
51
3.8
Fan Control
Outline
Fan control is carried out according to the following priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control when cooling operation
5. Tap control when drooping function is working
6. Fan control when forced operation
7. Fan control in low noise mode
8. Fan control during heating operation
9. Fan control in the quiet mode
10.Fan control in the powerful mode
11.Fan control for pressure difference upkeep
Detail
Fan OFF Control when Stopped
Fan OFF delay for 60 seconds must be made when the compressor is stopped.
3.9
Moisture Protection Function 1
(Securing of Differential
Pressure and Blown Air Temperature)
Outline
To secure the reliability of the compressor (for dryness of suction refrigerant and differential
pressure) which is the primary purpose of the compressor, the lower limit of the output
frequency is limited to two stages under the condition of outside air temperature. This time, in
addition to this purpose, this function is adopted also for prevention of cold draught by securing
the blown air temperature at the time of heating operation by low-temperature out side air.
Processing
1. At the first step
���
During operation of compressors.
���
Outdoor temperature
≤
DOA1CG
If
���
and
���
are under the simultaneous condition with AND, the lower limit of frequency in
this function is set at FCG7.
���
Compressors stop.
���
Outdoor temperature
≥
DOA2CG
If
���
and
���
are under the simultaneous condition with OR, the lower limit of frequency at the
first step control is cancelled.
2. At the second step
���
During operation of compressors
���
Outdoor temperature
≤
DOA3CG
If
���
and
���
are under the simultaneous condition with AND, the lower limit of frequency in
this function is set at FCG8.
���
Compressors stop.
���
Outdoor temperature
≥
DOA4CG
If
���
and
���
are under the coordinate condition with OR, the lower limit of frequency at the
second step control is cancelled.
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...