Outdoor Unit
SiBE04-302
152
Removal Procedure
2. Outdoor Unit
2.1
Removal of
External Casing
Procedure
Warning Be sure to turn off all power supplies at least 10 min. before
disassembling work.
Step
Procedure
Points
1
The
stop valve cover
can be removed when
the fixed screw is
removed.
As three hooks are provided,
slide the cover downward to
remove.
The forced cooling operation
in the pumping down mode
can be carried out by
pushing the operation switch
on the main unit for five
seconds. (The existing
models can do it through the
switch on the PC board just
as well.)
The layout of the connection
ports for the flares has been
changed to horizontal
position from vertical
position.