Indoor Unit
SiBE04-302
144
Removal Procedure
1.5
Removal of
Heat Exchanger
Procedure
Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Conduct pump-down
operation.
Remove the installation
frame from the mounting
plate.
Warning!
If gas leaks, repair the leak
location, then connect all
refrigerant from the unit.
Conduct vacuum drying, and
charge proper amount of
refrigerant.
Warning!
Do not mix any gas (including
air) other than the specified
refrigerant (R410A) into
refrigerating cycle.
(Mixing of air or other gas
causes abnormal
temperature rise in
refrigerating cycle, and this
results in pipe rupture or
personal injuries.)
Pay attention so that the
residual drain will not make
a floor dirty.
In case that a drain hose is
buried inside a wall, remove
it after the drain hose in the
wall is pulled out.
1
Remove the drain hose.
Make curing so that the
residual drain water will
not leak out.
2
Disengage the
insulation tube and
disconnect the flare
nuts for the gas line and
the liquid line.
Use two wrenches to
disconnect pipe.
After pipes are
disconnected, close all pipe
openings with caps to
prevent dust and moisture
from entering pipes.
3
Disengage the indoor
unit from the installation
plate.
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...