![Daikin ARK25BVMB Service Manual Download Page 178](http://html.mh-extra.com/html/daikin/ark25bvmb/ark25bvmb_service-manual_501295178.webp)
SiBE04-302
Outdoor Unit
Removal Procedure
169
2.7
Removal of
Four Way Valve
and
Motor Valve
Procedure
Warning Be sure to turn off all power supplies at least 10 min. before disassembling work.
Step
Procedure
Points
1. Remove the parts around
the four way valve.
1
Remove the terminal
cover and the lead
wires of the
compressor so as not
to be burnt out by a gas
brazing machine.
2
Remove the thermistor
for the heat exchanger.
The thermistor for the heat
exchanger is fixed by a
clamp material at one
portion. Be sure to fix the
thermistor back on the
original position when
restoring.
Warning!
Ventilate when the refrigerant
leaks during the work. (If the
refrigerant is exposed to the
fire, it will cause toxic gas.)
3
Remove the four way
valve’s coil.
Pay attention so as not to
loose the retainer for the
thermistor.