Troubleshooting
SiBE04-302
110
Service Diagnosis
Troubleshooting
Check No.6
Refer to P.122
Check No.7
Refer to P.123
Check No.9
Refer to P.124
Turn off the power and turn it on
again.
Check No. 6
Check the thermistor resistance
value.
Replace the fin thermistor.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
(R2953)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Error again or outdoor unit
fan activated?
YES
l
Fin thermistor
NO
Slightly dirty
Check No. 9
Check the outdoor unit
fan or related.
Malfunctioning
Radiation fin dirty?
Too dirty
Functioning
Thermistor as
specified in its characteristic
chart?
Above 122˚C?
NO
YES
NO
YES
Check the radiation fin
temperature.
Check No. 7
Check the installation condition.
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 120˚C and stops itself
when it drops below 113˚C.
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...