SiBE04-302
Troubleshooting
Service Diagnosis
99
4.8
Compressor Lock
Remote
Controller
Display
E6
Method of
Malfunction
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Malfunction
Decision
Conditions
The system judges the compressor lock, and stops due to over current.
The system judges the compressor lock, and cannot operation with position detection within
15 seconds after start up.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Compressor locked
Troubleshooting
Note:
If the model doesn’t have SPM, replace the outdoor unit PCB.
Turn off the power. Disconnect the
harnesses U, V and W.
∗
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Replace the compressor.
(R2842)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
YES
System shut
down after errors repeated
several times?
NO
NO
Normal?
YES
Emergency stop
without compressor
running?
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and get the system restarted.
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...