SiBE04-302
Control Specification
Function and Control
49
3.4
Discharge Pipe Control
Outline
The discharge pipe temperature is used as the compressor's internal temperature. If the
discharge pipe temperature rises above a certain level, the operating frequency upper limit is
set to keep this temperature from going up further.
Detail
Divide the Zone
Management within the Zones
3.5
Input Current Control
Outline
Detect an input current by the CT during the compressor is running, and set the frequency
upper limit from such input current.
In case of heat pump model, this control is the upper limit control function of the frequency
which takes priority of the lower limit of four way valve activating compensation.
Detail
The frequency control will be made within the following zones.
When a “stop current” continues for 2.5 seconds after rushing on the stop zone, the compressor
operation stops.
If a “drooping current” is continues for 1.0 second after rushing on the drooping zone, the
frequency will be 2 Hz drooping.
Repeating the above drooping continues until the current rushes on the drooping zone without
change.
In the unchanged zone, the frequency limit will remain.
In the return / reset zone, the frequency limit will be cancelled.
Limitation of current drooping and stop value according to the outdoor air temperature
1. In case the operation mode is cooling
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
2. In case the operation mode is heating (only for heat pump model)
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
Zone
Control contents
Stop zone
When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone
Start the timer, and the frequency will be drooping.
Unchanged zone
Keep the upper limit of frequency.
Return / Reset zone
Cancel the upper limit of frequency.
A
B
C
D
(R2836)
A
B
C
D
120
103
101
80
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...