Troubleshooting
SiBE04-302
108
Service Diagnosis
Troubleshooting
Check No.6
Refer to P.122
P4
:
Radiation fin thermistor
J3
:
Discharge pipe temperature thermistor
J6
:
Outdoor unit heat exchanger temperature thermistor
H9
:
Outdoor air temperature thermistor
Turn on the power again.
Reconnect.
Reconnect.
Replace defective one(s) of
the following thermistors.
l
Radiation fin thermistor
l
Discharge pipe
temperature thermistor
l
Outdoor unit heat
exchanger temperature
thermistor
l
Outdoor air thermistor
Replace the following
thermistor.
l
Indoor unit heat
exchanger thermistor
Replace the outdoor unit
PCB. (Replace the indoor
unit PCB.)
(R2849)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Error displayed again
on remote controller?
NO
YES
YES
YES
NO
Indoor unit
heat exchanger thermistor
functioning?
NO
Connector or thermistor
disconnected?
NO
YES
Normal?
Check No. 6
Check the thermistor resistance
value.
Check No. 6
Check the indoor unit heat
exchanger thermistor resistance
value in the heating mode.
Summary of Contents for ARK25BVMB
Page 17: ...Functions SiBE04 302 8 List of Function ...
Page 31: ...Specifications SiBE04 302 22 Specifications ...
Page 137: ...Check SiBE04 302 128 Service Diagnosis ...
Page 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Page 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Page 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Page 199: ...SiBE04 302 iv Index ...