11
|
Configuration
Installer reference guide
194
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
Description
[9.3.5]
[6‑04]
▪
The capacity difference between the second
and first step of the backup heater at nominal
voltage. Nominal value depends on backup
heater configuration.
Equilibrium
#
Code
Description
[9.3.6]
[5-00]
Equilibrium
: Is backup heater operation
allowed above equilibrium temperature during
space heating operation?
▪
1: NOT allowed
▪
0: Allowed
[9.3.7]
[5-01]
Equilibrium temperature
: Outdoor
temperature below which operation of the
backup heater is allowed.
Range: –15°C~35°C
INFORMATION
Above 10°C ambient temperature, the heat pump will operate until 55°C. Configuring
a higher setpoint with an ambient temperature that is higher than the set
equilibrium temperature will prevent the backup heater from assisting. The backup
heater will ONLY assist if you increase the equilibrium temperature [5‑01] to the
required ambient temperature you need to reach the higher setpoint.
Operation
#
Code
Description
[9.3.8]
[4‑00]
Backup heater operation:
▪
0:
Restricted
▪
1:
Allowed
▪
2:
Only DHW
: Backup heater operation is
enabled for domestic hot water and disabled
for space heating.
Booster heater
Capacity
The capacity of the booster heater must be set for the energy metering and/or
power consumption control feature to work properly. When measuring the
resistance value of the booster heater, you can set the exact heater capacity and
this will lead to more accurate energy data.
#
Code
Description
[9.4.1]
[6‑02]
Capacity
[kW]. Only applies to domestic hot
water tank with an internal booster heater. The
capacity of the booster heater at nominal
voltage.
Range: 0~10 kW