11
|
Configuration
Installer reference guide
202
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
Description
[9.8.5]
N/A
Restriction:
Only applicable if [9.8.4]=
Smart
grid
.
Shows the Smart Grid operation mode sent by
the 2 incoming Smart Grid contacts.
Smart grid operation mode
:
▪
Free running
▪
Forced off
▪
Recommended on
▪
Forced on
See also below table (Smart Grid operation
modes).
[9.8.6]
N/A
Restriction:
Only applicable if [9.8.4]=
Smart
grid
.
To set if electrical heaters are allowed.
Allow electrical heaters
:
▪
No
▪
Yes
[9.8.7]
N/A
Restriction:
Only applicable in case of room
thermostat control, and if [9.8.4]=
Smart grid
.
To set if room buffering will be enabled.
Enable room buffering
:
▪
No
: The extra energy from the photovoltaic
panels is only buffered in the DHW tank (i.e.
heat up the DHW tank).
▪
Yes
: The extra energy from the photovoltaic
panels is buffered in the DHW tank, and in the
space heating/cooling circuit (i.e. heat up or
cool down the room).