11
|
Configuration
Installer reference guide
151
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
NOTICE
If the room
Antifrost
setting is active and a U4 error occurs, the unit will
automatically start the
Antifrost
function via the backup heater. If the backup
heater is not allowed for room frost protection during a U4 error, the room
Antifrost
setting MUST be disabled.
NOTICE
Room frost protection.
Even if you turn OFF space heating/cooling operation ([C.2]:
Operation
>
Space heating/cooling
), room frost protection operation –if
enabled– can still activate. However, for leaving water temperature control and
external room thermostat control, the protection is NOT guaranteed.
For more detailed information about room frost protection in relation to the
applicable unit control method, see the sections below.
Leaving water temperature control ([C‑07]=0)
Under leaving water temperature control, room frost protection is NOT
guaranteed. However, if room antifrost [2‑06] is activated, limited frost protection
by the unit is possible:
If...
Then...
▪
Space
heating/cooling
=
Off
,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
Space heating/cooling
=
On
, and
▪
Operation mode
=
Heating
The unit will supply leaving water to the
heat emitters to heat up the room
according to normal logic.
▪
Space heating/cooling
=
On
, and
▪
Operation mode
=
Cooling
There is no room frost protection.
External room thermostat control
([C‑07]=1)
Under external room thermostat control, room frost protection is guaranteed by
the external room thermostat, provided that:
▪
[C.2]
Space heating/cooling
=
On
, and
▪
[9.5.1]
Emergency
=
Automatic
or
auto SH normal/DHW off
.
However, if [1.4.1]
Antifrost
is activated, limited frost protection by the unit is
possible.
In case of 1 leaving water temperature zone:
If...
Then...
▪
Space
heating/cooling
=
Off
,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.