3/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
3.6
[0-06]
R/W
25~43°C, step: 1°C
35°C
3.6
[0-07]
R/W
10~25°C, step: 1°C
20°C
Additional zone
3.7
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─
Setpoint range
3.8.1
[9-05]
R/W
15~37°C, step: 1°C
25°C
3.8.2
[9-06]
R/W
[2-0D]=2:
37~60, step: 1°C
60°C
[2-0D]
≠
2:
37~55, step: 1°C
55°C
3.8.3
[9-07]
R/W
5~18°C, step: 1°C
7°C
3.8.4
[9-08]
R/W
18~22°C, step: 1°C
22°C
Additional zone
3.A
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
└─
Delta T
3.B.1
[1-0C]
R/W
[2-0D]
≠
2 (Radiator)
3~10°C, step: 1°C
5°C
[2-0D] = 2 (Radiator)
8°C
3.B.2
[1-0E]
R/W
3~10°C, step: 1°C
5°C
Space heating / cooling
└─
Operation range
4.3.1
[4-02]
R/W
14~35°C, step: 1°C
with BUH:
35°C
without BUH:
25°C
4.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
Space heating / cooling
4.4
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
4.5
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
4.6
[E-02]
R/W (*4)
R/O (*3)
0: Reversible (*4)
1: Heating only (*3)
4.7
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 80~50%
5~8 : 80~50% during sampling
6
Space heating / cooling
4.9
[F-00]
R/W
0: Restricted
1: Allowed
4.A
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B
[9-04]
R/W
1~4°C, step: 1°C
4°C
4.C
[2-06]
R/W
0: Disabled
1: Enabled
Tank
5.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
50°C
5.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.6
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
5.7.1
[2-01]
R/W
0: No
1: Yes
5.7.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
5.7.3
[2-02]
R/W
0~23 hour, step: 1 hour
1
5.7.4
[2-03]
R/W
55~75°C, step: 5°C
70°C
5.7.5
[2-04]
R/W
5~60 min, step: 5 min
10 min
Tank
5.8
[6-0E]
R/W
40~75°C, step: 1°C
60°C
[E-07]=0
40~80°C, step: 1°C
60°C
[E-07]=5
5.9
[6-00]
R/W
2~40°C, step: 1°C
27°C
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Emitter type
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
Thermostat type
Delta T heating
Delta T cooling
Space heating OFF temp
Space cooling OFF temp
Number of zones
Pump operation mode
Unit type
Pump limitation
Pump outside range
Increase around 0°C
Overshoot
Room frost protection
Comfort setpoint
Eco setpoint
Reheat setpoint
Heat up mode
Activation
Operation day
Start time
Tank setpoint
Duration
Maximum
Hysteresis
(*1) *V3/W1
(*2) *3V3/3W1
(*3) EDLA*
(*4) EBLA*
(#) Setting is not applicable for this unit.
4P627273-1 - 2020.09
Summary of Contents for ALTHERMA
Page 277: ...11 11 ...
Page 278: ......
Page 279: ......
Page 280: ...4P620241 1 2020 06 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...