6
|
Application guidelines
Installer reference guide
32
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
NOTICE
Certain types of fan coil units –in this document referred to as "heat pump
convectors"–, are able to receive input of the outdoor unit operation mode (cooling
or heating X2M/3 and X2M/4) and/or to send output of the heat pump convector
thermostatic condition (main zone: X2M/30 and X2M/35; additional zone: X2M/30
and X2M/35a).
The application guidelines illustrate the possibility of receiving or sending digital
input/output. This functionality can only be used in case the heat pump convector
has such features and the signals meet following requirements:
▪
Output of outdoor unit (input to heat pump convector): cooling/heating
signal=230 V (cooling=230 V, heating=0 V).
▪
Input to outdoor unit (output of heat pump convector): thermostat ON/OFF
signal=voltage-free contact (closed contact=thermo ON, open contact=thermo
OFF).
6.2 Setting up the space heating/cooling system
The heat pump system supplies leaving water to heat emitters in one or more
rooms.
Because the system offers a wide flexibility to control the temperature in each
room, you need to answer the following questions first:
▪
How many rooms are heated or cooled by the heat pump system?
▪
Which heat emitter types are used in each room and what is their design leaving
water temperature?
Once the space heating/cooling requirements are clear, we recommend to follow
the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the
room frost protection. However, the room frost protection is only possible if [C.2]
Space heating/cooling
=
On
.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be
guaranteed in all conditions, then you have to set
Emergency
[9.5.1] to one of the
following:
▪
Automatic
▪
auto SH reduced/DHW on
▪
auto SH reduced/DHW off
▪
auto SH normal/DHW off
NOTICE
An overpressure bypass valve can be integrated in the system. Keep in mind that this
valve might not be shown on the illustrations.
Summary of Contents for ALTHERMA
Page 277: ...11 11 ...
Page 278: ......
Page 279: ......
Page 280: ...4P620241 1 2020 06 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...