Configuration
Installer reference guide
207
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
Description
[9.A.2]
[D‑09]
Electricity meter 2
:
▪
0
None
: NOT installed
▪
1
1/10kWh
: Installed
▪
2
1/kWh
: Installed
▪
3
10/kWh
: Installed
▪
4
100/kWh
: Installed
▪
5
1000/kWh
: Installed
In case of pulse meter for photovoltaic panels:
▪
6
100/kWh for PV panel
: Installed
▪
7
1000/kWh for PV panel
: Installed
Sensors
External sensor
#
Code
Description
[9.B.1]
[C–08]
External sensor
: When an optional external
ambient sensor is connected, the type of the
sensor must be set.
▪
0
None
: NOT installed. The thermistor in the
user interface and in the outdoor unit are used
for measurement.
▪
1
Outdoor
: Connected to the hydro PCB of the
outdoor
unit
measuring
the
outdoor
temperature
.
Remark:
For some functionality,
the temperature sensor in the outdoor unit is
still used.
▪
2
Room
: Connected to the hydro PCB of the
outdoor
unit
measuring
the
indoor
temperature
. The temperature sensor in the
user interface is NOT used anymore.
Remark:
This value has only meaning in room
thermostat control.
Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.
You can calibrate the external outdoor ambient temperature sensor. It is possible
to give an offset to the thermistor value. This setting can be used to compensate
for situations where the external outdoor ambient sensor cannot be installed on
the ideal installation location.
#
Code
Description
[9.B.2]
[2-0B]
Ext. amb. sensor offset
: Offset on the
ambient temperature measured on the external
outdoor temperature sensor.
▪
–5°C~5°C, step 0.5°C