![background image](http://html.mh-extra.com/html/daikin/altherma/altherma_installers-reference-manual_501163077.webp)
8
|
Piping installation
Installer reference guide
77
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
NOTICE
When circulation in each space heating/cooling loop is controlled by remotely
controlled valves, it is important that the minimum water volume is guaranteed,
even if all of the valves are closed.
M2
b
c
b
b
M3
M1
d
a
a
User interface (delivered as accessory)
b
Individual room thermostat (option)
c
Overpressure bypass valve (field supply)
d
Shut-off valve (delivered as accessory)
M1...3
Individual motorised valve to control each loop (field supply)
Maximum water volume
NOTICE
The maximum water volume depends on whether glycol is added to the water
circuit. For more information on the addition of glycol, refer to
Use the following graph to determine the maximum water volume for the
calculated pre-pressure.
20
2.4
2.1
1.8
1.5
1.2
0.9
1
0.6
0.3
70
120
170
200 220
270
290
320
A
B
A
Pre-pressure (bar)
B
Maximum water volume (l)
Water
Water + glycol
Example: Maximum water volume and expansion vessel pre-pressure
Summary of Contents for ALTHERMA
Page 277: ...11 11 ...
Page 278: ......
Page 279: ......
Page 280: ...4P620241 1 2020 06 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...