![background image](http://html.mh-extra.com/html/daikin/altherma/altherma_installers-reference-manual_501163095.webp)
9
|
Electrical installation
Installer reference guide
95
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Item
Description
Human Comfort Interface
See:
▪
Installation and operation manual of the
Human Comfort Interface
▪
Addendum book for optional equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9]
Control
[1.6]
Room sensor offset
(in case of DHW tank)
3‑way valve
See:
▪
Installation manual of the 3-way valve
▪
Addendum book for optional equipment
Wires: 3×0.75 mm²
Maximum running current: 100 mA
[9.2]
Domestic hot water
(in case of DHW tank)
Domestic hot water tank
thermistor
See:
▪
Installation manual of the domestic hot
water tank
▪
Addendum book for optional equipment
Wires: 2
The thermistor and connection wire (12 m)
are delivered with the domestic hot water
tank.
[9.2]
Domestic hot water
(in case of DHW tank)
Power supply for booster
heater (from outdoor unit
to thermal protector of
booster heater)
See:
▪
Installation manual of the domestic hot
water tank
▪
Addendum book for optional equipment
Wires: (2+GND)×2.5 mm²
[9.4]
Booster heater
(in case of DHW tank)
Power supply for booster
heater (from mains to
outdoor unit)
See:
▪
Installation manual of the domestic hot
water tank
▪
Addendum book for optional equipment
Wires: 2+GND
Maximum running current: 13 A
[9.4]
Booster heater
Summary of Contents for ALTHERMA
Page 277: ...11 11 ...
Page 278: ......
Page 279: ......
Page 280: ...4P620241 1 2020 06 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...