Electrical installation
Installer reference guide
111
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
2
Push the rear plate on each of the 4 spots where the snap-fits are located.
9.2.6 To connect the shut-off valve
INFORMATION
Shut-off valve usage example.
In case of one LWT zone, and a combination of
underfloor heating and heat pump convectors, install a shut-off valve before the
underfloor heating to prevent condensation on the floor during cooling operation.
For more information, see the installer reference guide.
Wires: 2×0.75 mm²
Maximum running current: 100 mA
230 V AC supplied by PCB
—
1
Open the service cover. See
72].
2
Connect the valve control cable to the appropriate terminals as shown in the
illustration below.
NOTICE
Only connect NO (normally open) valves.
X2M.3
X2M.4
M2S
(NO)
Summary of Contents for ALTHERMA