The outdoor unit is designed for outdoor installation only, and for the following
ambient temperatures:
Cooling mode
10~43°C
Heating mode
▪
For models with integrated backup heater or if the
external backup heater kit is installed:
–25~35°C
▪
Otherwise:
–25~25°C
DHW production
–25~35°C
Mind the measurement guidelines:
Maximum height difference between domestic hot water tank
and outdoor unit
5 m
Maximum distance between outdoor unit and…
domestic hot water tank
10 m
3-way valve
10 m
external backup heater kit
10 m
Special requirements for R32
The outdoor unit contains an internal refrigerant circuit (R32), but you do NOT
have to do any refrigerant field piping, or refrigerant charging.
Mind the following requirements and precautions:
WARNING
▪
Do NOT pierce or burn.
▪
Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
▪
Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater).