5
|
Application guidelines
Installer reference guide
38
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Changeover to external heat source decided by an auxiliary contact
▪
Only possible in external room thermostat control AND one leaving water
temperature zone (see
"5.2 Setting up the space heating/cooling system"
24]).
▪
The auxiliary contact can be:
-
An outdoor temperature thermostat
-
An electricity tariff contact
-
A manually operated contact
-
…
▪
Setup: Connect the following field wiring:
L
N
H
Com
A
K2A
K1A
X2M
BTI
K2A
K1A
Indoor/Auto/Boiler
35 30
X Y
Indoor
B
TI
Boiler thermostat input
A
Auxiliary contact (normally closed)
H
Heating demand room thermostat (optional)
K1A
Auxiliary relay for activation of indoor unit (field supply)
K2A
Auxiliary relay for activation of boiler (field supply)
Indoor
Indoor unit
Auto
Automatic
Boiler
Boiler
NOTICE
▪
Make sure the auxiliary contact has enough differential or time delay to prevent
frequent changeover between indoor unit and auxiliary boiler.
▪
If the auxiliary contact is an outdoor temperature thermostat, install the
thermostat in the shadow so that it is NOT influenced or turned ON/OFF by direct
sunlight.
▪
Frequent changeover may cause corrosion of the auxiliary boiler. Contact the
manufacturer of the auxiliary boiler for more information.