9
|
LAN adapter
Installer reference guide
125
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
ON" operation mode, there is NO power limitation: the system selects the comfort
setpoint for space heating/cooling, and will heat up the domestic hot water tank to
the maximum temperature. The unit’s compressor and the electrical heaters are
not limited in their power consumption.
The "Forced ON" operation mode is particularly useful in case of energy
management systems that react to low energy tariffs, in case of grid overload
(signaled by the energy distributor to the energy management system), or when
multiple houses are connected to the grid that are controlled simultaneously, this
to stabilise the grid.
INFORMATION
Once running in one of the Smart Grid operation modes, the system will keep
running in that mode until the input state of the LAN adapter is changed.
9.5.3 System requirements
The Smart Grid application poses the following requirements to the heat pump
system:
Item
Requirement
LAN adapter software
It is recommended to ALWAYS keep the LAN adapter
software up-to-date.
Unit control method
On the user interface, make sure to set [2.9]=2
(
Control
=
Room thermostat
)
Domestic hot water
settings
To allow for energy buffering in the domestic hot
water tank, on the user interface, make sure to set
[9.2.1]=4 (
Domestic hot water
=
Integrated
).
Power consumption
control settings
On the user interface, make sure to set:
▪
[9.9.1]=1 (
Power consumption control
=
Continuous
)
▪
[9.9.2]=1 (
Type
=
kW
)
9.6 Troubleshooting – LAN adapter
9.6.1 Overview: Troubleshooting
This chapter describes what to do in case of problems.
It contains information about:
▪
Solving problems based on symptoms
▪
Solving problems based on error codes
9.6.2 Solving problems based on symptoms – LAN adapter
Symptom: Cannot access the web page
Possible causes
Corrective action
The LAN adapter is not powered
(heartbeat LED not blinking).
Make sure that the LAN adapter is
correctly connected to the indoor unit,
and that the power of all connected
equipment is turned ON.