activate the ON/OFF pump of the mixing valve station ONLY when there is
demand.
#
Code
Description
[2.D.2]
[F-0C]
The shut off valve:
▪
0
No
: is NOT influenced by heating or cooling
demand.
▪
1
Yes
: closes when there is NO heating or
cooling demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room
thermostat request setting (NOT in case of leaving water temperature setting).
During cooling
: If [F‑0B] is enabled, the shut off valve closes when the unit is
running in cooling operation mode. Enable this setting to avoid cold leaving water
through the heat emitter and the forming of condensation (e.g. under floor heating
loops or radiators).
#
Code
Description
[2.D.2]
[F-0C]
The shut off valve:
▪
0
No
: is NOT influenced by changing the space
operation mode to cooling.
▪
1
Yes
: closes when the space operation mode
is cooling.
10.5.4 Additional zone
Setpoint screen
Control the leaving water temperature for the additional zone via setpoint screen
[3]
Additional zone
.
See
136].
Schedule
Indicates if the desired leaving water temperature is according to a schedule.
See
150].
#
Code
Description
[3.1]
N/A
Schedule
▪
No
▪
Yes
Heating schedule
Define a heating temperature schedule for the additional zone via [3.2]
Heating
schedule
.
See
"10.3.7 Schedule screen: Example"
Cooling schedule
Define a cooling temperature schedule for the additional zone via [3.3]
Cooling
schedule
.
See