14 Troubleshooting
Contact
For the symptoms listed below, you can try to solve the problem yourself. For any
other problem, contact your installer. You can find the contact/helpdesk number
via the user interface.
1
Go to [8.3]:
Information
>
Dealer information
.
14.1 Overview: Troubleshooting
Before troubleshooting
Carry out a thorough visual inspection of the unit and look for obvious defects such
as loose connections or defective wiring.
14.2 Precautions when troubleshooting
WARNING
▪
When carrying out an inspection on the switch box of the unit, ALWAYS make
sure that the unit is disconnected from the mains. Turn off the respective circuit
breaker.
▪
When a safety device was activated, stop the unit and find out why the safety
device was activated before resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default setting. If you are unable to
find the cause of the problem, call your dealer.
DANGER: RISK OF ELECTROCUTION
WARNING
Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this
appliance MUST NOT be supplied through an external switching device, such as a
timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
DANGER: RISK OF BURNING
14.3 Solving problems based on symptoms
14.3.1 Symptom: The unit is NOT heating as expected
Possible causes
Corrective action
The temperature setting is NOT correct Check the temperature setting on the
remote controller. Refer to the
operation manual.