8
|
Electrical installation
Installer reference guide
90
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
3
Fix the cable with cable ties to the cable tie mountings.
8.2.4 To connect the electricity meters
Wires: 2 (per meter)×0.75 mm²
Electricity meters: 12 V DC pulse detection (voltage supplied by PCB)
[9.A]
Energy metering
INFORMATION
In case of an electricity meter with transistor output, check the polarity. The positive
polarity MUST be connected to X5M/6 and X5M/4; the negative polarity to X5M/5
and X5M/3.
1
"6.2.2 To open the indoor unit"
55]):
1
Top panel
1
3
2
2
User interface panel
3
Installer switch box cover
2
Connect the electricity meters cable to the appropriate terminals as shown in
the illustration below.
S3S
S2S
3
4
5
6
2×
1×
X5M
1×
5 6
3 4
3
Fix the cable with cable ties to the cable tie mountings.
8.2.5 To connect the domestic hot water pump
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A
(continuous)
[9.2.2]
DHW pump
[9.2.3]
DHW pump schedule