10
|
Configuration
Installer reference guide
162
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
#
Code
Description
[3.6]
[0-04]
[0-05]
[0-06]
[0-07]
Set weather-dependent cooling:
Note:
There are 2 methods to set the weather
143]. Both curve types require 4 field
settings to be configured according to the figure
below.
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪
T
t
:
Target
leaving
water
temperature
(additional zone)
▪
T
a
: Outdoor temperature
▪
[0-07]: Low outdoor ambient temperature.
10°C~25°C
▪
[0-06]: High outdoor ambient temperature.
25°C~43°C
▪
[0-05]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be higher than [0‑04]
as for low outdoor temperatures less cold
water is required.
▪
[0-04]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be lower than [0‑05] as
for high outdoor temperatures colder water is
required.
Emitter type
For more information about
Emitter type
150].
#
Code
Description
[3.7]
[2‑0D]
Emitter type
▪
0:
Underfloor heating
▪
1:
Fancoil unit
▪
2:
Radiator
The setting of the emitter type has an influence on the space heating setpoint
range and the target delta T in heating as follows: