13
|
Maintenance and service
Installer reference guide
215
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Prerequisite:
Open all the hot water tapping points to allow air to enter the
system.
Prerequisite:
Remove the top panel. See
"6.2.2 To open the indoor unit"
1
Remove the tube from the temperature and pressure relief valve that is
located on top of the tank.
2
Remove the temperature and pressure relief valve from the tank.
3
Use a drain hose and a pump to drain the tank via the access point.
2
1
4
Tightening torques for installation:
Item
Tightening torque
Tube connection
30 N•m
Temperature and pressure relief valve
40 N•m
13.4 To inspect the inside of the domestic hot water tank
DANGER: RISK OF BURNING
The water in the tank can be very hot.
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Close the cold water supply.
Prerequisite:
Open all the hot water tapping points to allow air to enter the
system.
Prerequisite:
Remove the top panel. See
"6.2.2 To open the indoor unit"
1
Remove the clip that fixes the domestic hot water OUT pipe.
2
Disconnect the pipe such that the tank is accessible for visual inspection (e.g.
with an endoscope).