Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.1.6
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
22°C
[2-0C]=1
35°C
[2-0C]=2
25°C
9.1.7
[1-06]
R/W
10~25°C, step: 1°C
20°C
9.1.7
[1-07]
R/W
25~43°C, step: 1°C
35°C
9.1.7
[1-08]
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
9.1.7
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
└─ Additional zone
9.1.8.1
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1.8.3
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
9.1.8.4
R/W
0: No
1: Yes
9.1.9
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
22°C
[2-0C]=1
35°C
[2-0C]=2
25°C
9.1.9
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
45°C
[2-0C]=1
55°C
[2-0C]=2
65°C
9.1.9
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.1.9
[0-03]
R/W
-40~5°C, step: 1°C
-40°C
9.1.A
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
9.1.A
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
9.1.A
[0-06]
R/W
25~43°C, step: 1°C
35°C
9.1.A
[0-07]
R/W
10~25°C, step: 1°C
20°C
└─ Tank
9.1.B.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.1.B.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.1.B.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.5
[6-08]
R/W
2~20°C, step: 1°C
10°C
└─ Domestic hot water
9.2.1
[E-05]
[E-06]
[E-07]
R/W
No DHW
Integrated
9.2.2
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
└─ Back up heater
9.3.1
[E-03]
R/O
4: 9W
9.3.2
[5-0D]
R/W
0: 230V, 1~
2: 400V, 3~
9.3.6
[5-00]
R/W
0: Allowed
1: Not allowed
9.3.7
[5-01]
Equilibrium temperature
R/W
-15~35°C, step: 1°C
0°C
9.3.8
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
9.3.9
[4-07]
R/W
[5-0D]=2: 0~9 kW, step 1 kW
9 kW
[5-0D]
≠
2: 0~6 kW, step 1 kW
6 kW
Installer settings
└─ Emergency
9.5.1
[4-06]
R/W
0: Manual
1: Automatic (normal SH/ DHW ON)
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.5.2
[7-06]
R/W
0: Disabled
1: Enabled
└─ Balancing
9.6.1
[5-02]
R/W
0: Disabled
1: Enabled
9.6.2
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.6.4
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour
9.6.5
[8-00]
R/W
0~20 min, step 1 min
1 min
Reheat hysteresis
Maximum BUH capacity
HP Forced OFF
Emergency
Space heating priority
Priority temperature
Anti-recycle timer
Minimum running timer
Operation
Low ambient temp. for LWT add zone cooling WD curve.
Heat up mode
Comfort setpoint
Eco setpoint
Reheat setpoint
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
DHW pump
BUH type
Voltage
BUH allowed above the equilibrium temperature?
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Emitter type
Setpoint mode
Schedule
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Domestic hot water
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
(*1) *X*_(*2) *H*
(#) Setting is not applicable for this unit.
4P569818-1A - 2019.10