5
|
Application guidelines
Installer reference guide
28
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Setting
Value
External room thermostat for the
main
zone:
▪
#: [2.A]
▪
Code: [C-05]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Benefits
▪
Cooling.
The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
▪
Efficiency.
Optimal energy efficiency because of the interlink function.
▪
Stylish.
Combination: Underfloor h Heat pump convectors
▪
Space heating is provided by:
-
The underfloor heating
-
The heat pump convectors
▪
Space cooling is provided by the heat pump convectors only. The underfloor
heating is shut off by the shut-off valve.
Setup
M1
B
A
b
a
A
Main leaving water temperature zone
B
One single room
a
Remote controller of the heat pump convectors
b
Remote outdoor sensor
▪
For more information about connecting the electrical wiring to the unit, see
"8.2 Overview of electrical connections for external and internal
actuators"
80].
▪
The heat pump convectors are directly connected to the indoor unit.
▪
A shut-off valve (field supply) is installed before the underfloor heating to
prevent condensation on the floor during cooling operation.
▪
The desired room temperature is set via the remote controller of the heat pump
convectors.
▪
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).