10
|
Configuration
Installer reference guide
186
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
#
Code
Description
[9.5.1]
N/A
▪
0:
Manual
▪
1:
Automatic
▪
2:
auto SH reduced/DHW on
▪
3:
auto SH reduced/DHW off
▪
4:
auto SH normal/DHW off
INFORMATION
If a heat pump failure occurs and
Emergency
is not set to
Automatic
(setting 1),
the room frost protection function, the underfloor heating screed dryout function,
and the water pipe antifreeze function will remain active even if the user does NOT
confirm emergency operation.
HP forced off
HP forced off
mode can be activated to allow the backup heater to provide
domestic hot water and space heating. This is, for example, useful when the brine
circuit is not yet ready to be used. Cooling is NOT possible when this mode is
activated.
#
Code
Description
[9.5.2]
[7-06]
Activation of the
HP forced off
mode
▪
0:
disabled
▪
1:
enabled
NOTICE
Activating
HP forced off
mode will NOT stop or prevent the brine pump from
operating in the following conditions:
▪
10 day brine pump operation
is active
▪
The
Brine pump
test run has been started
▪
Passive cooling is active
Balancing
Priorities
For systems with an integrated domestic hot water tank
#
Code
Description
[9.6.1]
[5‑02]
Space heating priority
: Defines
whether backup heater will assist the heat
pump during domestic hot water operation.
For optimal operation and lowest power
consumption, it is strongly recommended to
keep the default setting (
0
).
If the backup heater operation is limited
([4‑00]=0) and the outdoor temperature is
lower than setting [5‑03], the domestic hot
water will not be heated with the backup
heater.