SiEN12-710A
Outdoor Unit
Removal Procedure
159
3
Disconnect the
connector for the fan
motor [S70].
"
For removal procedure of the
lead wire for the fan motor,
refer to “Removal of the
PCB”.
4
Detach the lead wire for
the fan motor.
5
Disconnect the
connector for the gas
pipe thermistor [S91]
and for the liquid pipe
thermistor [S92].
[S91] : Gas pipe thermistor
(white)
[S92] : Liquid pipe thermistor
(red)
6
Disconnect the
connector for the
overheating protector
[S40].
[S40] : Overheating protector
Step
Procedure
Points
[S70]
(R7578)
(R7579)
[S92]
[S91]
(R7580)
[S40]
(R7581)