Troubleshooting
SiEN12-710A
142
Service Diagnosis
4.23 Anti-icing Function in Other Rooms / Unspecified
Voltage (between Indoor and Outdoor Units)
Remote Control
Display
UA, UH
Method of
Malfunction
Detection
A wrong connection is detected by checking the combination of indoor and outdoor units on the
microcomputer.
Malfunction
Decision
Conditions
"
Operation halt due to the anti-icing function in other rooms
"
Operation halt due to unspecified voltage between indoor and outdoor units
Supposed
Causes
"
Operation halt due to the anti-icing function in other rooms
"
Wrong connections at the indoor unit
"
PCB wrongly connected
Troubleshooting
(R7151)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
NO
YES
NO
YES
Error-
displaying air-conditioner
running?
Supply voltage as specified?
Normal?
Check the model number.
Check the combination of all the
models being connected.
The anti-icing function is
activated in other rooms.
Refer to A5.
Correct.
Reconnect.