Troubleshooting
Service Diagnosis
125
4.13 High Pressure Control in Cooling
Remote Control
Display
F6
Method of
Malfunction
Detection
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the
temperature being sensed by the heat exchanger thermistor exceeds the limit.
Malfunction
Decision
Conditions
"
Activated when the temperature being sensed by the heat exchanger thermistor rises above
65°C.
"
Deactivated when the temperature drops below 53°C.
Supposed
Causes
"
The installation space is not large enough.
"
Faulty outdoor unit fan
"
Faulty electronic expansion valve
"
Faulty outdoor unit heat exchanger thermistor
"
Faulty outdoor unit PCB
"
Faulty stop valve
"
Dirty heat exchanger